Assembly Components

Assembly Components

Acoustical

STC 57

NOAL 18-0748

Fire

1 hour

U425

6” Thick, 8.5 lb/ft2

Download Test Report

Description

  • 1-5/8” Type S screws spaced 8” o.c. at edges and 12” o.c. in the field.

  • Face layer 5/8” type X (FLAME CURB®, PABCO® Glass Sheathing) gypsum panel applied vertically.

  • 1-1/4” Type S screws (for fire 1" Type S drywall Screws) spaced 8” o.c. at edges and 12” o.c. in the field.

  • Base layer 5/8” type X (FLAME CURB®, PABCO® Glass Sheathing) gypsum panel applied vertically.

  • 3-5/8” 43 mil (18 ga.) steel studs, 16” o.c.

  • 3-1/2” glass fiber insulation in stud space.

  • Resilient channel applied at right-angle, 24” o.c.

  • 1/2" Type S screw attaching resilient channel to stud at each intersection.

  • One Layer 5/8” QuietRock® ES or QuietRock® ES MR type X gypsum panel applied vertically.

  • 1” #6 Type S screws spaced 12” o.c. in the field.